Tyco F3200 Manual do Utilizador Página 147

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 284
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 146
Document No: LT0122 F3200 Installation & Programming Manual
Installation & Wiring
Issue 2.7 5 July 2001 Page 8-9
FIG 8.2.2
GOOSENECK CABLING
8.2.2 MAINS WIRING
The mains (240Vac) supply must be connected in accordance with AS1670.1 and AS3000
regulations.
Ensure the mains cables to the FIP are isolated at the
Distribution Board
before connecting to the FIP.
The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind
the mains cover.
(a) Remove the mains cover with a Pozi screw-driver.
(b) Shape the mains cable to fit through the grommet in the slot in the top of the cover,
cut to length and strip only 20mm of the PVC cable sheath.
(c) Connect the wires: blue (black) to N
brown (red) to A
green/yellow (green) to E
Take care when stripping not to "nick" wires.
(d) Cable tie the cable to the cabinet.
(e) Refit the mains cover .
Vista de página 146
1 2 ... 142 143 144 145 146 147 148 149 150 151 152 ... 283 284

Comentários a estes Manuais

Sem comentários